2CP50-71-22 Pressure Sensor
The Sensata 2CP50-71-22 Pressure Sensor is a perfect solution designed for high-pressure HVAC and refrigeration loops. Featuring a sealed gauge pressure range of 0–590 psia, this 2cp50 71 22 unit ensures precise monitoring in harsh industrial environments. Its plated steel construction and HNBR sealing technology provide superior resistance to corrosion and compatibility with modern low-GWP refrigerants.

Product Features
2CP50-71-22
Ceramic Capacitive Technology
The core of the 2CP50-71-1 is its ceramic capacitive sensing element, which ensures high stability and resistance to harsh refrigerants, offering long-term accuracy in challenging industrial environments.
Temperature Compensation
Designed for extreme conditions, the sensor operates reliably in temperatures ranging from -40°C to +135°C, ensuring data integrity whether used in sub-freezing suction lines or high-temperature discharge lines.
High Reliability Design
Equipped with overvoltage, short circuit and reverse voltage protection, strong EMC immunity and ESD protection.
Flexible Configuration
Optional gauge/absolute/sealed gauge measurement types, two connection materials and two seal materials.
Technical Specifications
2cp50 71 22
| Parameter | Details |
|---|---|
| Product Series | Sensata 2CP50 |
| Pressure Range | 0-590 psi (approx. 40.7 bar), Sealed Gauge |
| Accuracy | ±1.5% *F.S. |
| Total Error Band | ±1.0%(-20°C~+85°C);±1.5%(-40°C~+125°C) |
| Operating Temperature | -40°C ~ +135°C |
| Supply Voltage | 4.5V~5.5V DC |
| Output Signal | 0.5V~4.5V DC(typical) |
| Response Time | 10ms |
| Overvoltage Protection | 16V DC |
| Reverse Voltage Protection | -14V DC |
| Output Load | 10K ohms typical |
| Pressure Port | 1/4″ SAE Female Flare with Deflator (7/16-20 UNF-2B) |
| Pressure Connection Material | HNBR or Neoprene options available |
| Enclosure Rating | IP65 |
Applications
sensata pressure 2cp50 71 42
Commercial HVAC Rooftop Units
Equipment Model: Carrier 30GT Series Rooftop Packaged Unit (cooling capacity: 5–25 tons, R454a refrigerant).
Installation Location: High-pressure refrigerant loop (between compressor discharge port and condenser inlet).
Functional Role: Monitors real-time discharge pressure (normal operating range: 250–550 psia). When pressure exceeds 580 psia (due to dirty condenser coils or refrigerant overcharge), the sensor triggers the unit’s “high-pressure protection” to unload the compressor, avoiding damage.
Supermarket Cascade Refrigeration
Equipment Model: Danfoss VLT Refrigeration Drive + Supermarket Cascade Refrigeration Rack (R454b refrigerant, for walk-in freezers and display cases).
Application Value: As a sealed gauge pressure sensor, it accurately measures the high-pressure side pressure of the cascade system (max 590 psia), coordinating with electronic expansion valves to maintain stable refrigerant flow, reducing energy consumption by ~8% compared to traditional pressure switches (based on HVAC industry efficiency data).
Industrial Factory HVAC Systems
Equipment Scenario: Large-scale factory assembly line HVAC (e.g., automotive manufacturing plants, with high electromagnetic interference from welding machines and conveyor motors).
Adaptation Advantage: The sensor’s 100 V/m EMC immunity prevents false signals caused by electromagnetic noise, ensuring stable control of the factory’s central air conditioning chilled water system (e.g., matching York YVAA series chillers for pressure feedback).
Compressor Discharge Monitoring
Serves as a critical feedback node for variable frequency drive (VFD) compressors, providing the real-time 10ms response data required to adjust motor speeds dynamically for load matching.
Related 2CP50 Models
sensata pressure sensors
- 2CP50-71-1
- Core Specs: Pressure range (0-750 psia), plated steel housing, EMC immunity (100 V/m, 1 MHz-512 MHz); see 2CP50-71-1 pressure sensor
- Application: Industrial environments with strong electromagnetic interference (such as factory HVAC systems) for high-pressure monitoring.
- 2CP50-71-4
- Core Specs: Entry-level high-pressure measurement (0-520 psia), cost-effective, plated steel material;
- Compatibility: Adapted to R404a refrigerant;
- Application: Commercial refrigeration (e.g., convenience store walk-in freezers) with basic high-pressure monitoring needs.
- 2CP50-71-106
- Core Specs: Absolute pressure measurement (0-750 psia), analog voltage output (0.5V-4.5V), plated steel material, cylindrical threaded housing;
- Compatibility: Suitable for high-pressure refrigeration loops (e.g., R410a, R32 refrigerants);
- Application: Industrial-grade HVAC systems (such as large centrifugal chillers) requiring high-pressure monitoring.
- 2CP50-71-52
- Core Specs: Pressure range (0-600 psia), plated steel housing, HNBR seal;
- Compatibility: Adapted to low-GWP refrigerants (e.g., R454a, R454b);
- Application: Commercial refrigeration systems (such as supermarket cascade refrigeration units) with medium-to-high pressure demands.
- 2CP50-71-53
- Core Specs: Full-range measurement (0-650 psia), plated steel construction, temperature-compensated design;
- Application: Heavy-duty refrigerated transport (e.g., container refrigeration units) for monitoring high-pressure refrigerant discharge lines.
- 2CP50-71-6
- Core Specs: Pressure range (0-550 psia), optimized for R134a refrigerant;
- Application: Medium-to-high pressure commercial air conditioning systems (such as rooftop packaged units for large shopping malls).
- 2CP50-71-8
- Core Specs: High burst pressure (2500 psi), pressure range (0-600 psia), plated steel material;
- Application: Industrial water-cooled chillers (e.g., York YVAA series) for monitoring compressor discharge pressure.
- 2CP50-71-9
- Core Specs: Pressure range (0-620 psia), compatible with R410a refrigerant, short-circuit and overvoltage protection (16 VDC);
- Protection Rating: NEMA 4X/IP65;
- Application: Outdoor HVAC equipment for compressor staging and unloading control in high-pressure loops.
- 2CP50-71-11
- Core Specs: Pressure range (0-580 psia), fast response time (10 ms), temperature-compensated;
- Application: Industrial centrifugal chillers (e.g., Carrier 30HXC series) for real-time control of electronic expansion valves.
- 2CP50-71-15
- Core Specs: Pressure range (0-630 psia), Neoprene seal;
- Compatibility: Suitable for low-carbon refrigeration systems (e.g., CO₂ transcritical cycles);
- Application: Monitoring high-pressure side pressure in environmentally friendly refrigeration systems.
After-Market & OEM Association
HVAC pressure sensors
2CP50-71-22 is often used as a replacement or original component for:
- Carrier OEM Replacement: Compatible with Carrier’s high-pressure sensor part number “HK 05 SZ 003” (for 30GT/30GX series rooftop units).
- York After-Market: Can replace York’s original high-pressure sensor (part number “024-32988-000“) in YVAA series chillers, with identical interface and performance.
Ready to Impletment in Your Application?
Our applications engineers work with you to design the optimal solution for yourspecific requirements, Get expert consultation and custom configuration support.
Request a Quote
Get a customized solution for your application!
FAQ
2cp5 Pressure Transducer
What is the difference between the 2CP5 and 2CP50 series?
The primary difference lies in the pressure range. The 2CP5 is designed for applications up to 500 psi, while the 2CP50 series is utilized for pressures above 500 psi, extending up to 750 psi
Which refrigerants are compatible with the HNBR seal?
The HNBR (Hydrogenated Nitrile) seal is compatible with R134a, R404a, R407c, R410a, and R507. If you are using R12 or R22, Neoprene seals are generally recommended.
Does the sensor require a specific mating connector?
Yes, the 2CP50-71-1 typically utilizes a Packard Metri-Pack electrical connection, designed to mate with Packard connector #12065287 for a secure, IP65-rated seal.
What pressure port and connection materials are available, and do they match standard industrial fittings?
A: The pressure port is 1/4″ SAE female flare (with deflator) + 7/16″-20 UNF-2B. Connection materials include brass (2CP5-exclusive) or plated steel — aligned with common industrial fitting standards.